Print

Digital inputs: How to wire digital inputs

How to wire digital inputs?

The Ace PLC can interface any DC voltage signal between 3 and 30 VDC. Typical system designs utilize 5 V, 12 V or 24 VDC.

  • Any connection to DC voltage between 1.5 and 30 VDC is sensed as a ‘1’.
    • Above 2.2 V, it is guaranteed to be a ‘1’
  • Any connection to ground (or voltage below 1.5 VDC) or an open connection is sensed as ‘0’.
    • Below 0.8 V, it is guaranteed to be a ‘0’
  • The ground reference of the signal must be connected to the ground terminal pin next to signal 1, or to the PLC’s input power ground.
  • ACE digital inputs are NPN transistor inputs. NPN Inputs = Positive logic.
  • The last pin on each digital input port connector provides a voltage (connected to the 5V power input, through a 10 ohm resistor and a diode) which is used by the Optocouple Input Terminal modules. It can also be used to supply “wetting voltage” to dry contact inputs.
  • Internally, as part of the protection circuit, each digital input is pulled to ground through a 10K ohm resistor. This pull down resistor ensures that the digital input shows up as inactive when nothing is connected or the connection just sources voltage when it is active.

The logic is the following:

  • When the  INPUT  is linked to VDC (+), the input = 1
  • When the  INPUT  is not connected to anything or the voltage is less than 0.8 VDC, the input = 0
Your sensor (here, the dry contact) must be connected to:

  •  (+) 
  •  INPUT

 

The ACE inputs are connected:

  •  (-)  > GND (-)
  • INPUT  > Your sensor

 (+)  is not used or only for dry contacts. It comes from the 5V, through a 10 ohm resistor and a diode.  It is current limited (by the resistor) and is nominally 4.3V

  • VDC (+) is the + of your power supply. From 3 to 30 VDC.
  • GND (-) is the – of your power supply.
  •  (+)  it is often the last pin of your connector
  •  (-)  it is often the first pin of your connector
  • INPUT  is an input of your ACE PLC

How to wire the input to a dry contact (Push button, relay contact,..)?

with a external voltage

Nothing on the  (+)  of the ACE PLC!

with voltage provide by the ACE PLC

Do not use this 5 VDC to power anything

 

How to wire the ACE input to an encoder or sensor?

PNP sensor
or NPN sensor with an internal pull-up resistor

Sensor switch to positive (24 VDC)

 

NPN sensor
without an internal pull-up resistor

Sensor switch to negative (0 VDC)
Some entry-level sensors do not include a pull-up resistor.

Read more: What sort of typical digital input signals that may be connected to the ACE digital inputs?

  • Switches, buttons, limit switches, etc.. :
    • Connect one side to positive DC power (from a supply whose ground is connected to the PLC ground)
    • Connect the other side of the switch to the digital input
  • Transistor signal or Encoders:
    • For transistor signals that supply voltage when on : connect sensor output to digital input
    • For transistor signals that switch to ground when on : connect to sensor output to digital inputs & if input device does not pull high when inactive, also pull up to positive voltage through a pull up resistor
  • Logic level signals:
    • Make sure that the signal’s ground reference is connected to the PLC ground. Connect of input.
    • Make sure that the signal switches high and low.

 

Mechanical contact bounce

ACE digital inputs and the ACE CPU are very fast. For a small program, the logic scan and input scan can occur 5 times per millisecond. At this rate, mechanical contact bounce can signal the program that an input is changing rapidly – which can be a problem.

To remedy this situation, vBuilder has an option to allow you to filter the digital inputs.

Note that debounce does not apply to inputs configured as high speed pulse counter inputs.

High speed pulse counters

Using vBuilder, 3 high speed pulse counters can be configured for:

  • basic high speed pulse counting (one digital input)
  • quadrature pulse counting (two digital inputs)

The same signal level requirements apply, as listed above.

Digital AC signals inputs: 24 VAC or 120 VAC

For digital inputs that are AC signals, the ACE’s digital input ports can be connected to Velocio Optocoupled Input Terminal Block modules.

A cable, supplied with each terminal block module is then connected to the ACE digital input port.

The Optocoupler Input Terminal Block modules convert the AC signals to the proper DC levels to the PLC.